314
Explicit Messages Appendix A
Note (1) The Instance ID specifies the Slice I/O Unit’s unit number (1 to 64).
(2) Specifies input 0.
(3) Specifies input 1.
Setting and Reading for Analog Output Units
Sampling
Cycle Set-
ting
Write/
Read
Sets the sampling cycle
for obtaining the rate of
change based on the
previous value.
Write:
10 hex
Read:
0E hex
8F hex 01 to 40
hex
*1
86 hex
*2
AE hex
*3
GRT1-AD2:
2 bytes (10
to 65535)
GRT1-AD2:
2 bytes (10 to
65535)
Cumulated
Value Read
Read/
Reset
Reads the cumulated
analog input value.
Read:
0E hex
Reset:
35 hex
8F hex 01 to 40
hex
*1
87 hex
*2
AF hex
*3
4bytes
(214748364.8
to
214748364.7)
Cumulative
Counter
Flag Read
Read Reads the cumulative
count status in the
Cumulative Counter
Flag in the area for
Generic Status Flags.
0: Counter overflow
1: Counter underflow
7: Set value overflow
Read:
0E hex
8F hex 01 to 40
hex
*1
88 hex
*2
B0 hex
*3
1 byte
Cumulative
Counter
Monitor
Value Set-
ting
Write/
Read
Writes/reads the set
monitor value for the
cumulative counter.
Write:
10 hex
Read:
0E hex
8F hex 01 to 40
hex
*1
89 hex
*2
B1 hex
*3
4 bytes 4 bytes
Cumulative
Counter
Unit Setting
Write/
Read
Sets the unit for the
cumulative counter.
0: Hour (count hours);
1: Minute (count
minutes)
Write:
10 hex
Read:
0E hex
8F hex 01 to 40
hex
*1
8A hex
*2
B2 hex
*3
1 byte 1 byte
Explicit
message
Read
/write
Function Command Response
Service
code
Class
ID
Instance
ID
Attribute ID Data
Explicit
message
Read
/write
Function Command Response
Service
code
Class
ID
Instance
ID
Attribute
ID
Data Size
Setting the
Number of
DA Conver-
sion Points
Write/
Read
Sets the number of DA
conversion points.
Write:
10 hex
Read:
0E hex
90 hex 01 to 40
hex
*1
64 hex 2 bytes 1 byte
Analog Out-
put Value
Read
Read Reads analog output
values.
0E hex 90 hex 01 to 40
hex
*1
67 hex
*2
7D hex
*3
2 bytes
Output
Range Set-
ting
Write/
Read
Sets the output range.
4 to 20 mA: 0;
0 to 10 V: 1;
0 to 20 mA: 2;
10 to 10 V: 3;
0 to 5 V: 4;
1 to 5 V: 6
0E hex 90 hex 01 to 40
hex
*1
68 hex
*2
7E hex
*3
1 byte