316
Explicit Messages Appendix A
Note (1) The Instance ID specifies the Slice I/O Unit’s unit number (1 to 64).
(2) Specifies output 0.
(3) Specifies output 1.
Explicit Messages for Temperature Input Units
Cumulative
Counter
Monitor
Value Set-
ting
Write/
Read
Writes/reads the set
monitor value for the
cumulative counter.
Write:
10 hex
Read:
0E hex
90 hex 01 to 40
hex
*1
79 hex
*2
8F
*3
4 bytes 4 bytes
Cumulative
Counter
Unit Setting
Write/
Read
Sets the unit for the
cumulative counter.
0: Hour (count hours);
1: Minute (count min-
utes)
Write:
10 hex
Read:
0E hex
90 hex 01 to 40
hex
*1
7A hex
*2
90 hex
*3
1 byte
Explicit
message
Read
/write
Function Command Response
Service
code
Class
ID
Instance
ID
Attribute
ID
Data Size
Explicit
message
Read
/write
Function Command Response
Service
code
Class
ID
Instance
ID
Attribute
ID
Data
Display
Format
Read (Nor-
mal or
1/100)
Read Reads the display for-
mat.
Normal display: 0
1/100 display: 1
0E hex 8F hex 01 to 40
hex
*1
65 hex 1 byte
Tempera-
ture Data
Value Read
for Normal
Display
Read Reads the value of tem-
perature data.
0E hex 8F
hex
*2
90
hex
*3
01 to 40
hex
*1
9A hex 2 bytes
Tempera-
ture Data
Value Read
for 1/100
Display
Read Reads the value of tem-
perature data.
0E hex 8F
hex
*2
90
hex
*3
01 to 40
hex
*1
6B hex 4 bytes
Input Type
Set
Write/
Read
Sets the input type.
GRT1-TS2P:
PT100 (−200 to 850
°C)
= F hex
PT100 (−200 to 200
°C)
= 11 hex
GRT1-TS2PK:
PT1000 (−200 to
850
°C) =13 hex
PT1000 (−200 to
200
°C) =14 hex
GRT1-TS2T:
R = 00 hex, S = 01 hex,
K1 = 02 hex, K2 = 03
hex, J1 = 04 hex, J2 =
05 hex, T = 06 hex, E =
07 hex, L1 = 08 hex, L2
= 09 hex, U = 0A hex, N
= 0B hex, W = 0C hex,
B = 0D hex, PL2 = 0E
hex
Write:
10 hex
Read:
0E hex
8F
hex
*2
90
hex
*3
01 to 40
hex
*1
97 hex 1 byte 1 byte