EasyManua.ls Logo

Omron SmartSlice GRT1 Series - Page 342

Omron SmartSlice GRT1 Series
366 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
322
Explicit Messages Appendix A
Digital Input
Mainte-
nance
Counter
Read Reads the total
ON time (unit: s)
or number of con-
tact operations
(unit: operations)
of the digital
input.
0E hex 8E hex 01 to 40
hex
*1
66 hex --- 4 bytes
0000 0000 to
FFFF FFFF hex
(0 to
4,294,967,295
decimal)
Write Writes the total
ON time (unit: s)
or number of con-
tact operations
(unit: operations)
for the digital
input.
10 hex 8E hex 01 to 40
hex
*1
66 hex 4 bytes
0000 0000 to
FFFF FFFF hex
(0 to
4,294,967,295
decimal)
---
Reset Resets the total
ON time (unit: s)
or number of con-
tact operations
(unit: operations)
of the digital
input.
05 hex 8E hex 01 to 40
hex
*1
66 hex --- ---
Digital Input
Mainte-
nance
Counter Set
Value
Read Reads the set
value for the total
ON time (unit: s)
or number of con-
tact operations
(unit: operations)
of the digital
input.
0E hex 8E hex 01 to 40
hex
*1
67 hex --- 4 bytes
0000 0000 to
FFFF FFFF hex
(0 to
4,294,967,295
decimal)
Write Writes the set
value for the total
ON time (unit: s)
or number of con-
tact operations
(unit: operations)
for the digital
input.
10 hex 8E hex 01 to 40
hex
*1
67 hex 4 bytes
0000 0000 to
FFFF FFFF hex
(0 to
4,294,967,295
decimal)
---
Input Power
Supply
Monitor
Read Reads the status
of the input power
supply.
If there is more
than one input
power supply, an
AND of the sta-
tus of all the input
power supplies is
returned.
0E hex 8E hex 01 to 40
hex
*1
70 hex --- 1 byte
00 hex: ON
01 hex: OFF
Explicit
message
Read/
write
Function Command Response
Service
code
Class
ID
Instance
ID
Attribute
ID
Data size

Table of Contents

Related product manuals