3-3. Link Controller Initialization
11/98 3-9 U3-1021
Westinghouse Proprietary Class 2C
9. Run RLCEXTPC.EXE using the command line syntax shown below:
RLCEXTPC.EXE [port] [baud]
where:
port = COM1 or COM2 (default = COM1)
baud = 9600 or 19200 (default = 19200 with no jumper installed)
Note
If a baud rate of 9600 is desired, install a wire jumper
in the Base Unit terminal block of the LC module
between B7 and B8.
For example, the following command line specifies that the LC is linked to
COM1 and that the baud rate is 19200:
A:\>RLCEXTPC.EXE COM1 19200
If the port and baud rate are not specified, the default values will apply
(port = COM1, baud = 19200).
10. Reset the LC module by removing it from its Base Unit, waiting five seconds,
and then replacing it. This will cause the LC to initialize itself and then to load
DOS from the floppy disk.
After DOS is loaded, the following will occur:
The screen on the PC will display the A:\> prompt.
DOS is executing on the LC card.
The external floppy is known as Drive A.
The internal disk on the LC card is known as Drive B.