39
Advanced (Dierent wiring congurations will display dierent):
1. Heat/Cool Dissipation Time
When the heating/cooling stops, the fan shuts o with a delay.
2. Compressor Protect Time
A time countdown to protect compressor when starting frequently.
3. Compressor Min Outdoor Temp
When the outdoor temperature is below this temperature, the
compressor will not be used. If you have auxiliary heating, it will use aux
heat to heat your home.
4. Compressor/(Aux) Heat Min On Time
Compressor/(Aux) Heat min on time during heating/cooling cycles.
5. Compressor/(Aux) Heat Stage 2 Temperature Delta
When the difference between the indoor temperature and the target
temperature reaches this value, the second stage is automatically turned
on.
6. Compressor/(Aux) Heat Stage 1 Max Runtime
If the rst stage fails to reach the target temperature after this time, the
second stage will be automatically turned on.
7. Aux Heat Max Outdoor Temp
Auxiliary heat is turned on only when the outdoor temperature is below
this value.