Manual Packo Ice Builders 10
26H7
Lamp
(Model
dependant)
ThKa Compressor 2
OK
Indicates when compressor 2
(cooling unit 1) is running.
On : when ThKa is closed and
HP is closed and BP is closed
and cooling is active
Cooling unit 2-4 (Model dependant)
31H1
Lamp
Tension
Ok
Main switch on Cooling unit 2
- 0: off
- 1: on
30S1
Switch
0 1
Control circuit Cooling unit 2
- 0: off
- 1: on
30S2
Knob
Boost function
cooling unit 1
- Push: built up once to
max. ice limits
30S3
Switch
Clock switch
cooling unit 1
- Auto: no clock is used
- Clock: Clock is used
30H1
Lamp
Cooling active
Liquid valve
- 0: off
- 1: on
31H3
Lamp
BP OK
On : when BP is closed and
Cooling is active
31H4
Lamp
HP Compressor 1
OK
On : when HP is closed and BP
is closed and cooling is active
31H6
Lamp
ThKa Compressor 1
OK
Indicates when compressor 1
(cooling unit 2) is running.
On : when ThKa is closed and
HP is closed and BP is closed
and cooling is active
31H5
Lamp
(Model
dependant)
HP Compressor 2
OK
On : when HP is closed and BP
is closed and cooling is active
31H7
Lamp
(Model
dependant)
ThKa Compressor 2
OK
Indicates when compressor 2
(cooling unit 2) is running.
On : when ThKa is closed and
HP is closed and BP is closed
and cooling is active
Ice water circuit
45S1
Switch
Ice water pump 1
M-0-A
- M: Manual operation
- 0: Pump off
- A: Automatic
operation