A rough determination of the sound pressure level L
Aeq
at a certain location at a distance r to the
heat pump can be calculated with the following formula and based on the sound power level L
Waeq
:
L
Aeq
= L
WAeq
+ 10 × log
(
Q
)
4 × π × r²
This only requires the direction factor Q in addition, which takes into account the spatial
propagation conditions of the sound source.
Direction factor Q for dierent arrangements of the sound source
Sound
propagation
In half space
(1 boundary: oor)
In quarter space
(2 boundaries: oor + 1 wall)
In eighth space
(3 boundaries: oor + 2 walls)
Q = 2 4 8
Arrangement
Example
The outdoor unit WH-UX16HE8 of a T-CAP bi-bloc system has a sound power level of 67 dB(A)
and is set up such that the sound can propagate in the quarter space (Q = 4). The sound pressure
level at 10 m distance is then:
L
Aeq
(10 m) = 67 dB (A) + 10 × log
(
4
)
= 42 dB (A)
4 × π × 10²
At a distance of 20 m, the sound pressure level is however still only:
L
Aeq
(20 m) = 67 dB (A) + 10 × log
(
4
)
= 36 dB (A)
4 × π × 20²
The sound pressure level can roughly be calculated even more easily by using the table below, by
subtracting the table value from the device-specic sound power level (→ 4.6.2.3 Technical Data
(bi-bloc systems), p. 40, → 4.6.3.3 Technical Data (mono-bloc systems), p. 55).
Table for rough determination of the sound pressure level based on the sound power level
Distance from the sound source (m)
Guide factor Q 1 2 4 5 6 8 10 12 15
2 -8 -14 -20 -22 -23.5 -26 -28 -29.5 -31.5
4 -5 -11 -17 -19 -20.5 -23 -25 -26.5 -28.5
8 -2 -8 -14 -16 -17.5 -20 -22 -23.5 -25.5