Judgement control:
o If outdoor ambient temperature < Heat to Cool Set Temperature, unit will operate in Heat Mode or else
the unit will operate in Cool Mode.
o If current operation is Cool mode, outdoor ambient temperature > Cool to Heat Temperature, unit will
maintain Cool mode operation or else the unit will operate Heat mode.
o If current operation is Heat mode, outdoor ambient temperature >Heat to Cool Temperature, unit will
maintain Heat mode operation or else the unit will operate Cool mode.
o Every 60 minutes the outdoor ambient temperature is judged.
o When Auto + Tank mode is selected, operation mode switching is judged by both outdoor ambient
temperature and indoor air temperature.
14.1.8 Auto Cooling Mode Operation Limit
10°
C
Compressor
ON
C
Compressor
OFF
Outdoor Ambient
Temperature
Auto Mode Cooling Only operation will start once the outdoor ambient temperature reaches 10°C and
compressor will continue to run until the outdoor ambient temperature drops to 8°C.
Due to this limitation,
If Heat to Cool temperature is set lower than 10°C, the compressor will not operates until the outdoor
ambient temperature reaches 10°C or higher.
14.1.9 Tank Mode Operation
3 ways valve direction
o 3 ways valve switch to tank side during Tank Thermo ON condition. Switch 3 ways valve to room side when
tank achieve Tank Thermo OFF temperature.
Tank Thermo ON/OFF Characteristic
Tank Thermo OFF
Case 1: Internal Tank Heater is select and Tank Heater ON
o Tank temperature > Tank Set Temperature continuously for 15 seconds. OR
o
Water outlet >75°C
Case 2: Tank Heater OFF OR External Heater is select
o When heat pump OFF due to water thermos & Tank temperature > Tank water set temperature for
continuously 20 seconds. OR
o
Tank temperature > Tank set temperature + 1°C for continuously 20 seconds.
Tank Thermo ON
Case 1: Tank Heater ON (Internal Tank Heater)
o Tank temperature < Tank set temperature + R/C (Tank re-heat temperature)
Case 2: Tank Heater OFF (Internal Tank Heater)
o Tank temperature < Tank water set temperature + R/C (Tank re-heat temperature)
* When tank thermo ON, water pump will ON for 3 minutes then only heat pump turn ON.
* Tank water set temperature = tank set temperature or 52°C whichever lower.
2 ways valve close
Heat pump Thermostat Characteristic
o
Heat pump Water Outlet set temperature is set to below table:
Outdoor ambient temperature Heat pump target water outlet temperature
< -10°C 56°C
> -10°C 59°C
Characteristic of heat pump thermos ON/OFF under tank mode condition: