18.4 Error Codes Table
Diagnosis display Abnormality/Protection control Abnormality judgement Primary location to verify
H00 No abnormality detected
H12 Indoor/Outdoor capacity unmatched 90s after power supply
Indoor/outdoor connection wire
Indoor/outdoor PCB
Specification and combination table in
catalo
g
ue
H15
Outdoor compressor temperature sensor
abnormality
Continue for 5 sec.
Compressor temperature sensor
(
defective or disconnected
)
H20 Water pump abnormality Continue for 10 sec.
Indoor PCB
Water pump
(
malfunction
)
H23
Indoor refrigerant liquid temperature
sensor abnormality
Continue for 5 sec.
Refrigerant liquid temperature sensor
(
defective or disconnected
)
H27 Service valve error Continue for 5 minutes
High pressure sensor (defective or
disconnected
)
H28 Abnormal solar sensor Continue for 5 sec.
Solar temperature sensor (defective or
disconnected
)
H31 Abnormal swimming pool sensor Continue for 5 sec.
Pool temperature sensor (defective or
disconnected
)
H36 Abnormal buffer tank sensor Continue for 5 sec.
Buffer tank sensor (defective or
disconnected
)
H38 Brand code not match
When indoor and outdoor
brand code not same
H42 Compressor low pressure abnormality
Outdoor pipe temperature sensor
Clogged expansion valve or strainer
Insufficient refrigerant
Outdoor PCB
Compresso
r
H43 Abnormal Zone 1 sensor Continue for 5 sec.
Water temperature Zone 1 senso
r
H44 Abnormal Zone 2 sensor Continue for 5 sec.
Water temperature Zone 2 senso
r
H62 Water flow switch abnormality Continue for 1 min.
Water flow switch
H63 Abnormal low pressure sensor 4 times in 20 minutes
Low pressure sensor (defective or
disconnect)
H64 Refrigerant high pressure abnormality Continue for 5 sec.
Outdoor high pressure sensor
(defective or disconnected)
H65 Abnormal deice water circulation
water flow > 7 l/min
continuously for 20 seconds
durin
g
anti freeze deice
Water pump
H67 Abnormal External Thermistor 1 Continue for 5 sec.
Room temperature Zone 1 senso
r
H68 Abnormal External Thermistor 2 Continue for 5 sec.
Room temperature Zone 2 senso
r
H70 Back-up heater OLP abnormality Continue for 60 sec.
Back-up heater OLP
(
Disconnection or activated
)
H72 Tank sensor abnormal Continue for 5 sec.
Tank senso
r
H74 PCB communication error
Communication or transfer
erro
r
Indoor main PCB and Sub PCB
H75 Low water temperature control
Room heater disable and deice
request to operate under low
water temperature
Heater operation must enable to
increase water temperature
H76
Indoor - control panel communication
abnormality
Indoor - control panel
(
defective or disconnected
)
H90 Indoor/outdoor abnormal communication > 1 min after starting operation
Internal/external cable connections
Indoor/Outdoor PCB
H91 Tank heater OLP abnormality Continue for 60 sec.
Tank heater OLP
(
Disconnection or activated
)
H95 Indoor/Outdoor wrong connection
Indoor/Outdoor supply voltage
H98 / F95
Outdoor high pressure overload
protection
Cooling high pressure overload
protection
Outdoor high pressure sensor
Water pump or water leakage
Clogged expansion valve or strainer
Excess refrigerant
Outdoor PCB
H99 Indoor heat exchanger freeze prevention
Indoor heat exchanger
Refri
g
erant shorta
g
e
F12 Pressure switch activate
4 times occurrence within
30 minutes
Pressure switch
F14 Outdoor compressor abnormal revolution
4 times occurrence within
20 minutes
Outdoor compressor
F15 Outdoor fan motor lock abnormality
2 times occurrence within
30 minutes
Outdoor PCB
Outdoor fan moto
r
F16 Total running current protection
3 times occurrence within
20 minutes
Excess refrigerant
Outdoor PCB