7 22 Aquarea air/water heat pump – Installation manual for compact systems 03 / 2013
Electrical installation
7 Electrical installation
Correct Incorrect Correct Incorrect Incorrect
10 mm ± 1
min. 5 mm
The clearance
between the
cables must be
at least 5 mm.
The insulation must be at least 10 mm +/- 1 mm in length. Ensure that all strands are clamped.
Clamping screw connection Tightening torque (NM)
M4 157 – 196
M5 196 – 245
Danger! 7KHZRUNPD\RQO\EHSHUIRUPHGE\TXDOLÀHGRUFHUWLÀHGSHUVRQQHO
Ensure that you have disconnected the power supply before you per-
form installation work. Secure the power supply to prevent unintentional
reactivation.
Ensure that all cables have the correct polarity. If this is not the case,
HOHFWULFVKRFNVRUÀUHFDQUHVXOW
Ensure that the cables can never come into contact with hot objects
such as the water pipes. High temperatures can damage the insulation.
2EVHUYHWKHIROORZLQJVSHFLÀFDWLRQVIRULQVWDOODWLRQ