11 – 53Aquarea air/water heat pump – Installation manual for compact systems 03 / 2013
11
Appendix
Appendix
Commissioning report
Commissioning report
Measurement report in heating mode after 20 min. runtime
Evaporation pressure
in bar
Machine voltage
in V L1-L2
Evaporation temperature
in °C
in V L1-L3
in V L2-L3
Suction gas temperature
in °C
Compressor current consumption
in A L1
Overheating
in K
in A L2
in A L3
Condensing pressure
in bar
Additional electric heater for heat pump current
consumption
in A L1
Condensing temperature
in °C
in A L2
in A L3
Liquid temperature
in °C
Electric immersion heater for hot-water tank current
consumption
in A L1
Compressor end temperature
in °C
RCD test
Mains connection 1 OK
Yes No
Outside temperature
in °C
Mains connection 2 OK
Yes No
Mains connection 3 OK
Yes No
Evaporator air intake temperature
in °C
Tank temperature
in °C
Evaporator air outlet temperature
in °C
Pressure drop in hydraulic system
in bar
Condenser water inlet temperature
in °C
High pressure switch triggers
Yes No
Switch-off point in bar
Condenser water outlet temperature
in °C
Switch-on point in bar
Low pressure switch triggers
Yes No
Switch-off point in bar
Switch-on point in bar
Flow rate cut-out triggers
Yes No