11 – 57Aquarea air/water heat pump – Installation manual for compact systems 03 / 2013
11
Appendix
Appendix
Error codes
Error code Error/Protection triggered Error recording
F12 Pressure switch triggered 4 times within 20 minutes
F14 Incorrect compressor speed 4 times within 20 minutes
F15 Incorrect speed of the outdoor unit fan Twice within 30 minutes
F16 Protection against excessive total operating current 3 times within 20 minutes
F20 Compressor overheating guard 4 times within 30 minutes
F22 Power transistor module overheating guard 3 times within 30 minutes
F23 Direct current peaks in the outdoor unit Occurred 7 times
F25 Problem switching between heating and cooling 4 times within 30 minutes
F27 Pressure switch 60 seconds long
F36 Outside temperature sensor 5 seconds long
F37 Return temperature sensor in indoor unit 5 seconds long
F40 Hot gas temperature sensor in the outdoor unit 5 seconds long
F41 PFC circuit 4 times within 10 minutes
F42 Temperature sensor of the heat exchanger in the outdoor unit 5 seconds long
F43 Outdoor unit defrosting temperature sensor 5 seconds long
F45 Supply temperature sensor in indoor unit 5 seconds long
F46 Current converter open in outdoor unit
F95 Cooling high pressure guard in outdoor unit
H12 Unsuitable output between the indoor and outdoor unit 90 seconds after supply of current
H15 Compressor temperature sensor 5 seconds long
H23 Liquid temperature sensor 5 seconds long
F24 Problems in the cooling circuit Twice within 20 minutes
H42 Compressor low pressure
H62 :DWHUVLGHÁRZUDWHFXWRXW 10 seconds long
H64 High-pressure sensor 5 seconds long
H70 OLP additional electric heater for heat pump 60 seconds long
H72 Hot water tank temperature sensor 5 seconds long
H76
&RPPXQLFDWLRQÀHOGVIRURSHUDWRUFRQWUROSDQHORQLQGRRUGHYLFH
H90
Communication errors between indoor and outdoor unit
60 seconds after start of operation
H91 OLP electric immersion heater for hot-water tank 60 seconds long
H95 Indoor/outdoor unit incorrectly connected
H98 High pressure guard in outdoor unit
H99 Antifreeze for indoor unit heat exchanger