EasyManua.ls Logo

Panasonic Aquarea WH-SDC16H6E5 - Hydraulic Balancing; Special Points Related to Cooling; Expansion Vessel

Panasonic Aquarea WH-SDC16H6E5
224 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
113
Aquarea air-to-water heat pumps - Planning and installation manual - 02/2022
Planning
5
Consideration of the nominal ow rate
For e󰀩cient heat generation, heat pumps use a temperature di󰀨erence of about 5 K between the
supply and return water ow. This distinguishes them from heat sources with boilers, which can
work without any problem with a temperature di󰀨erence of about 10 or 20 K between the supply
and return water ow. A consequence of the small temperature di󰀨erence in heat pumps is that the
ow rate of heat pumps, which is needed to transport the heat within the circuit, must be higher
than for heat sources with boilers with the same thermal output. The nominal ow rate and the
resulting resistance of the pipe network must therefore be given special attention at the time of
design.
Consideration of the nominal pipe width
The pressure drop in the pipe rises exponentially with the ow rate. This means that doubling the
ow rate causes the pressure drop to increase by a factor of 4. The decisive aspect for this is the
ow speed in the pipe that depends on the ow rate and inner diameter.
As an alternative to a pipe network calculation, a nomogram can be used to determine the pressure
drop across pipe segments. Recommendations for designing the main distribution circuit are:
The ow speed should be in the range of 0.3 to max. 1.5 m/s.
The pressure drop per metre should be about 0.1 kPa/m.
Based on these criteria, the required nominal pipe width can be read o󰀨 from the copper tube
nomogram. To determine the pipe network resistance of a complete pipe run, rst, the pressure
drop per metre must be multiplied by the length of each pipe segment, and then the pressure drops
of all segments must be summed up. The total resistance of a complete pipe run is obtained as the
total pressure drop of all pipe segments multiplied by a lump sum supplement factor of 1.5.
!
IMPORTANT
The total of the individual resistances of all components of the pipe network must not exceed the
pump discharge head for the nominal ow rate. If the pipe network resistance is too high, the unit’s
integrated water circulation pump cannot achieve the nominal ow rate. The heat pump control
functions will register a shortfall of the minimum circulation quantity and throw an alarm.
5.3.3 Hydraulic balancing
Hydraulic balancing of the heat transfer system is the process of optimising the set ow rates for
several pipe segments through regulating valves. This prevents individual building areas from being
excessively overheated, while other areas with a lower ow rate remain cold. Hydraulic balancing
therefore raises the living comfort and is, at the same time, also a requirement for e󰀩cient
operation of the air-to-water heat pump. Therefore, hydraulic balancing is also a prerequisite for the
nancial promotion of heat pumps.
5.3.4 Special points related to cooling
Hydraulically, a heat pump system with cooling mode does not di󰀨er from a heating-only system.
However, to correctly determine the total annual amount of heat and cold delivered by the heat
pump, which is needed to calculate the seasonal coe󰀩cient of performance, it is necessary to use
energy meters which record the amount of heat as well as the amount of cold.
5.3.5 Expansion vessel
The Aquarea heat pumps have an integral expansion vessel with a model-specic volume of 6 or
10 litres (see table) and an initial pressure of 1 bar.
The volume of the expansion vessel is adequate for heating systems whose total water quantity
and its static height (di󰀨erence of the highest point of the system to the expansion vessel) must not
exceed dened limits.

Table of Contents

Related product manuals