158 Aquarea air-to-water heat pumps - Planning and installation manual - 02/2022
Installation
6
Removing top cover plate and replacing it
Carry out the following steps to remove the top cover plate of the outdoor unit or mono-bloc unit:
1. Remove the xing screws (1) along the edge of the cover plate (2).
2. Lift the cover plate from the device (3).
3. To replace the top cover plate, proceed in the reverse order.
1
3
2
1
1
A WH-MDC05J3E5 mono-bloc unit is shown as an example.
For other outdoor and mono-bloc unit types*, proceed
similarly as appropriate.
* cfr. →1 Model range, p. 8
6.6 Connecting the refrigeration circuit
Note
For the installation of mono-bloc units, you can skip chapter 6.6 “Connecting the refrigeration
circuit”. Continue with section → 6.7 Connecting the heating circuit, p. 165.
Requirements for correctly congured are ttings
ATTENTION
Danger of leakages due to incorrect tool
Using a wrong tool, e.g. a pipe wrench, can deform or damage the are nut. This can cause
leakages.
► Use a suitable adjustable spanner or ring spanner.
Danger of leakages caused by exceeding the tightening torque
Too high a tightening torque can cause deformation and consequently leakages.
► Observe the correct torque when tightening the are nut (→ Permissible tightening
torques of refrigerant pipes (All in One units), p. 162, → Permissible tightening torques
of refrigerant pipes (Hydrokits), p. 163, → Permissible tightening torques of refrigerant
pipes (Outdoor units), p. 164).