55
Aquarea air-to-water heat pumps - Planning and installation manual - 02/2022
Product Description
4
4.6.3.3 Technical Data
Mono-bloc systems | Aquarea High Performance | J Generation | Single Phase | Heating and Cooling | R32
Single phase
Outdoor unit WH‑MDC05J3E5 WH‑MDC07J3E5 WH‑MDC09J3E5
Heating capacity / COP (A +7 °C, W 35 °C) kW / – 5.00 / 5.08 7.00 / 4.76 9.00 / 4.48
Heating capacity / COP (A +7 °C, W 55 °C) kW / – 5.00 / 3.01 7.00 / 2.82 8.95 / 2.78
Heating capacity / COP (A +2 °C, W 35 °C) kW / – 5.00 / 3.57 7.00 / 3.40 7.45 / 3.13
Heating capacity / COP (A +2 °C, W 55 °C) kW / – 5.00 / 2.27 6.30 / 2.16 7.00 / 2.12
Heating capacity / COP (A -7 °C, W 35 °C) kW / – 5.00 / 2.78 6.80 / 2.81 7.50 / 2.63
Heating capacity / COP (A -7 °C, W 55 °C) kW / – 5.00 / 1.85 6.30 / 1.86 7.00 / 1.80
Cooling capacity / EER (A 35 °C, W 7 °C) kW / – 5.00 / 3.31 7.00 / 3.06 9.00 / 2.71
Cooling capacity / EER (A 35 °C, W 18 °C) kW / – 5.00 / 5.05 7.00 / 4.73 9.00 / 4.25
ErP data for Space Heating
Average climate
Seasonalenergyefciency(ηs,h) W35 / W55 % 202 / 142 193 / 130 193 / 130
SCOP W35 / W55 5.12 / 3.63 4.90 / 3.32 4.90 / 3.32
Energy class
1
W35 / W55 A+++ / A++ A+++ / A++ A+++ / A++
Warm climate
Seasonalenergyefciency(ηs,h) W35 / W55 % 237 / 165 227 / 160 227 / 160
SCOP W35 / W55 6.00 / 4.20 5.75 / 4.07 5.75 / 4.07
Energy class
1
W35 / W55 A+++ / A+++ A+++ / A+++ A+++ / A+++
Cold climate
Seasonalenergyefciency(ηs,h) W35 / W55 % 160 / 115 164 / 116 164 / 116
SCOP W35 / W55 4.08 / 2.95 4.18 / 2.98 4.18 / 2.98
Energy class
1
W35 / W55 A++ / A+ A++ / A+ A++ / A+
Sound power
2
Heat dB(A) 59 59 59
Dimension H x W x D mm 865 x 1,283 x 320 865 x 1,283 x 320 865 x 1,283 x 320
Net weight kg 99 104 104
Refrigerant (R32) / CO
2
Eq.
3
kg / t 1.3 / 0.878 1.3 / 0.878 1.3 / 0.878
Water pipe connector Inch R 1¼ , R 1¼ , R 1¼ ,
Pump
Number of speeds Variable Speed Variable Speed Variable Speed
Input power (Min / Max) W 34 / 96 36 / 100 39 / 108
Heatingwaterow(∆T=5K.35°C) l/min 14.3 20.1 25.8
Capacity of integrated electric heater kW 3 3 3
Input power
Heat kW 0.985 1.47 2.01
Cool kW 1.51 2.29 3.32
Running and starting
current
Heat A 4.7 7.0 9.3
Cool A 7.0 10.5 14.7
Current 1 A 12 17 17
Current 2 A 13 13 13
Recommended fuse A 30 / 15 30 / 15 30 / 16
Recommended cable size, supply 1 / 2 mm² 3 x 1.5 / 3 x 1.5 3 x 2.5 / 3 x 1.5 3 x 2.5 / 3 x 1.5
Operation range
Outdoor ambient
Heat °C -20 ~ 35 -20 ~ 35 -20 ~ 35
Cool °C +10 ~ +43 +10 ~ +43 +10 ~ +43
Water outlet
Heat °C 20 ~ 60 20 ~ 60 20 ~ 60
Cool °C 5 ~ 20 5 ~ 20 5 ~ 20
1 Scale from A+++ to D.
2 Sound power in accordance to 811/2013, 813/2013 and EN12102-1:2017 at +7 °C.
3 WH-MDC models are hermetically sealed.
Note:
EER and COP calculation is based in accordance to EN14511.