EasyManua.ls Logo

Panasonic Aquarea WH-SDC16H6E5 - Technical Data

Panasonic Aquarea WH-SDC16H6E5
224 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
55
Aquarea air-to-water heat pumps - Planning and installation manual - 02/2022
Product Description
4
4.6.3.3 Technical Data
Mono-bloc systems | Aquarea High Performance | J Generation | Single Phase | Heating and Cooling | R32
Single phase
Outdoor unit WH‑MDC05J3E5 WH‑MDC07J3E5 WH‑MDC09J3E5
Heating capacity / COP (A +7 °C, W 35 °C) kW / – 5.00 / 5.08 7.00 / 4.76 9.00 / 4.48
Heating capacity / COP (A +7 °C, W 55 °C) kW / – 5.00 / 3.01 7.00 / 2.82 8.95 / 2.78
Heating capacity / COP (A +2 °C, W 35 °C) kW / – 5.00 / 3.57 7.00 / 3.40 7.45 / 3.13
Heating capacity / COP (A +2 °C, W 55 °C) kW / – 5.00 / 2.27 6.30 / 2.16 7.00 / 2.12
Heating capacity / COP (A -7 °C, W 35 °C) kW / – 5.00 / 2.78 6.80 / 2.81 7.50 / 2.63
Heating capacity / COP (A -7 °C, W 55 °C) kW / – 5.00 / 1.85 6.30 / 1.86 7.00 / 1.80
Cooling capacity / EER (A 35 °C, W 7 °C) kW / – 5.00 / 3.31 7.00 / 3.06 9.00 / 2.71
Cooling capacity / EER (A 35 °C, W 18 °C) kW / – 5.00 / 5.05 7.00 / 4.73 9.00 / 4.25
ErP data for Space Heating
Average climate
Seasonalenergyefciency(ηs,h) W35 / W55 % 202 / 142 193 / 130 193 / 130
SCOP W35 / W55 5.12 / 3.63 4.90 / 3.32 4.90 / 3.32
Energy class
1
W35 / W55 A+++ / A++ A+++ / A++ A+++ / A++
Warm climate
Seasonalenergyefciency(ηs,h) W35 / W55 % 237 / 165 227 / 160 227 / 160
SCOP W35 / W55 6.00 / 4.20 5.75 / 4.07 5.75 / 4.07
Energy class
1
W35 / W55 A+++ / A+++ A+++ / A+++ A+++ / A+++
Cold climate
Seasonalenergyefciency(ηs,h) W35 / W55 % 160 / 115 164 / 116 164 / 116
SCOP W35 / W55 4.08 / 2.95 4.18 / 2.98 4.18 / 2.98
Energy class
1
W35 / W55 A++ / A+ A++ / A+ A++ / A+
Sound power
2
Heat dB(A) 59 59 59
Dimension H x W x D mm 865 x 1,283 x 320 865 x 1,283 x 320 865 x 1,283 x 320
Net weight kg 99 104 104
Refrigerant (R32) / CO
2
Eq.
3
kg / t 1.3 / 0.878 1.3 / 0.878 1.3 / 0.878
Water pipe connector Inch R 1¼ , R 1¼ , R 1¼ ,
Pump
Number of speeds Variable Speed Variable Speed Variable Speed
Input power (Min / Max) W 34 / 96 36 / 100 39 / 108
Heatingwaterow(∆T=5K.35°C) l/min 14.3 20.1 25.8
Capacity of integrated electric heater kW 3 3 3
Input power
Heat kW 0.985 1.47 2.01
Cool kW 1.51 2.29 3.32
Running and starting
current
Heat A 4.7 7.0 9.3
Cool A 7.0 10.5 14.7
Current 1 A 12 17 17
Current 2 A 13 13 13
Recommended fuse A 30 / 15 30 / 15 30 / 16
Recommended cable size, supply 1 / 2 mm² 3 x 1.5 / 3 x 1.5 3 x 2.5 / 3 x 1.5 3 x 2.5 / 3 x 1.5
Operation range
Outdoor ambient
Heat °C -20 ~ 35 -20 ~ 35 -20 ~ 35
Cool °C +10 ~ +43 +10 ~ +43 +10 ~ +43
Water outlet
Heat °C 20 ~ 60 20 ~ 60 20 ~ 60
Cool °C 5 ~ 20 5 ~ 20 5 ~ 20
1 Scale from A+++ to D.
2 Sound power in accordance to 811/2013, 813/2013 and EN12102-1:2017 at +7 °C.
3 WH-MDC models are hermetically sealed.
Note:
EER and COP calculation is based in accordance to EN14511.

Table of Contents

Related product manuals