108 Aquarea air-to-water heat pumps - Planning and installation manual - 02/2022
Planning
5
Hydrokit H generation Hydrokit F generation
1
1
2
1
1
1
2
1
Minimum distances hydrokit H generation
1 Minimum distance: 100 mm
2 Minimum distance: 800 mm
Minimum distances hydrokit F generation
1 Minimum distance: 300 mm
2 Minimum distance: 600 mm
!
IMPORTANT
As the compressor is in the outdoor unit of the bi-bloc system, only the operation of the circulation
pump in the hydrokit or All in One unit needs to be taken into consideration as the cause for the
development of operating noise.
Example of an installation room with hydrokit and domestic hot water tank
Front view Top view
3
4
500
595 400400
200
200
200
1265
400400
~ 2,5
800
2500
1200
800
340
1
2
5
1
2
2100
3
4
500
595 400400
200
200
200
1265
400400
~ 2,5
800
2500
1200
800
340
1
2
5
1
2
2100
1 Domestic hot water tank
2 Hydrokit
3 Hot water outlet
4 Fresh water inlet
5 Door to the installation room
Note: Schematic gure for explanation purposes only.