50 Aquarea air-to-water heat pumps - Planning and installation manual - 02/2022
Product Description
4
Bi-bloc systems | Aquarea T-CAP | H Generation | Three Phase | Super Quiet | Heating and Cooling | R410A
Three phase (Power to indoor)
Kit KIT‑WQC09H3E8 KIT‑WQC12H9E8 KIT‑WQC16H9E8
Heating capacity / COP (A +7 °C, W 35 °C) kW / – 9.00 / 4.84 12.00 / 4.74 16.00 / 4.28
Heating capacity / COP (A +7 °C, W 55 °C) kW / – 9.00 / 2.94 12.00 / 2.88 16.00 / 2.71
Heating capacity / COP (A +2 °C, W 35 °C) kW / – 9.00 / 3.59 12.00 / 3.44 16.00 / 3.10
Heating capacity / COP (A +2 °C, W 55 °C) kW / – 9.00 / 2.21 12.00 / 2.19 16.00 / 2.13
Heating capacity / COP (A -7 °C, W 35 °C) kW / – 9.00 / 2.85 12.00 / 2.72 16.00 / 2.49
Heating capacity / COP (A -7 °C, W 55 °C) kW / – 9.00 / 2.02 12.00 / 1.92 16.00 / 1.86
Cooling capacity / EER (A 35 °C, W 7 °C) kW / – 7.00 / 3.17 10.00 / 2.81 12.20 / 2.57
Cooling capacity / EER (A 35 °C, W 18 °C) kW / – 7.00 / 5.19 10.00 / 5.13 12.20 / 3.49
ErP data for Space Heating
Average climate
Seasonalenergyefciency(ηs,h) W35 / W55 % 181 / 130 170 / 130 160 / 125
SCOP W35 / W55 4.59 / 3.32 4.32 / 3.32 4.08 / 3.20
Energy class
1
W35 / W55 A+++ / A++ A++ / A++ A++ / A++
Warm climate
Seasonalenergyefciency(ηs,h) W35 / W55 % 235 / 158 231 / 158 231 / 159
SCOP W35 / W55 5.95 / 4.02 5.86 / 4.02 5.86 / 4.05
Energy class
1
W35 / W55 A+++ / A+++ A+++ / A+++ A+++ / A+++
Cold climate
Seasonalenergyefciency(ηs,h) W35 / W55 % 160 / 125 160 / 125 150 / 125
SCOP W35 / W55 4.08 / 3.20 4.08 / 3.20 3.83 / 3.20
Energy class
1
W35 / W55 A++ / A++ A++ / A++ A++ / A++
Indoor unit WH‑SQC09H3E8 WH‑SQC12H9E8 WH‑SQC16H9E8
Sound pressure Heat / Cool dB(A) 33 / 33 33 / 33 33 / 33
Dimension H x W x D mm 892 x 500 x 340 892 x 500 x 340 892 x 500 x 340
Net weight kg 43 44 45
Water pipe connector Inch R 1¼ R 1¼ R 1¼
A class pump
Number of speeds Variable Speed Variable Speed Variable Speed
Input power (Min / Max) W 32 / 102 34 / 110 30 / 105
Heatingwaterow(∆T=5K.35°C) l/min 25.8 34.4 45.9
Capacity of integrated electric heater kW 3 9 9
Recommended fuse A 15 / 30 15 / 30 15 / 30
Recommended cable size, supply 1 / 2 mm² 5 x 1.5 / 3 x 1.5 5 x 1.5 / 5 x 1.5 5 x 1.5 / 5 x 1.5
Outdoor unit WH‑UQ09HE8 WH‑UQ12HE8 WH‑UQ16HE8
Sound power
2
Heat dB(A) 58 58 62
Dimension H x W x D mm 1,410 x 1,283 x 320 1,410 x 1,283 x 320 1,410 x 1,283 x 320
Net weight kg 151 151 161
Refrigerant (R410A) / CO
2
Eq. kg / t 2.85 / 5.951 2.85 / 5.951 2.99 / 6.243
Pipe diameter Liquid / Gas Inch (mm) 3/8 (9.52) / 5/8 (15.88) 3/8 (9.52) / 5/8 (15.88) 3/8 (9.52) / 5/8 (15.88)
Pipe length range m 3 ~ 30 3 ~ 30 3 ~ 30
Elevation difference (in/out) m 20 20 20
Pipe length for additional gas m 10 10 10
Additional gas amount g/m 50 50 50
Operation range
Outdoor ambient
Heat °C -28 ~ +35 -28 ~ +35 -28 ~ +35
Cool °C +16 ~ +43 +16 ~ +43 +16 ~ +43
Water outlet
Heat °C 20 ~ 60 20 ~ 60 20 ~ 60
Cool °C 5 ~ 20 5 ~ 20 5 ~ 20
1 Scale from A+++ to D.
2 Sound power in accordance to 811/2013, 813/2013 and EN12102-1:2017 at +7 °C.
Note: