11.4.6. Compressor Reverse Rotation Protection Control
If the compressor is operating continuously for 5 minutes or longer and the temperature difference between intake air and indoor
heat exchanger is 2.5°C or less for continuous 2 minutes, compressor will stop and restart automatically.
Time Delay Safety Control is activated before the compressor restart.
T = Intake air temperature - Indoor heat exchanger temperature
This is to prevent compressor from rotate reversely when there is an instantaneous power failure.
11.4.7. Dew Prevention control
To prevent dew formation at indoor unit discharge area.
This control will be activated if:-
- Cooling mode or Quiet mode.
- Remote Control setting temperature is less than 25°C.
- Fan speed is at Low or QLo.
- Room temperature is constant (±1°C) for 30 minutes.
- Compressor is continuously running.
Fan speed and angle of horizontal louver (vertical airflow angle) will be adjusted accordingly in this control.
- Fan speed will be increased slowly if the unit is in quiet mode but no change in normal cooling mode.
- The angle of horizontal louver will be changed as below figure.
Note:
A = Normal operation angle of rotation
B = Dew prevention angle of rotation
Horizontal Louver Angle
During Anti-Dew condensation prevention, the horizontal louver angle in Auto-control are as below figure.
During Anti-Dew condensation prevention, the horizontal louver angle in Manual control are as below figure.
Operation mode Airflow direction auto-control Airflow direction manual control
Cooling, Soft Dry A 12° ~ 32° 12°, 15°, 20°, 26°, 32°
B20° ~ 30° 22°, 24°, 26°, 28°, 30°