17.5.7 H23 (Indoor Pipe Temperature Sensor Abnormality)
Malfunction Decision Conditions
During startup and operation of cooling and heating, the temperatures detected by the indoor heat exchanger
temperature sensor are used to determine sensor errors.
Malfunction Caused
Faulty connector connection.
Faulty sensor.
Faulty PCB.
Troubleshooting
Sensor (Thermistor)
Characteristics
70
60
50
Resistance (kΩ)
Temperature (ºC)
40
30
20
10
-10 0 10 20 30 40 50
0
1 Pipe temp. Sensor
2 Intake Air Temp. Sensor
1
2
When abnormality indication starts again
Check the indoor air temperature sensor:
●
Plug out connector from the indoor unit PCB
●
Measure the resistance of the indoor intake air
temperature sensor
●
Defect in indoor intake air temperature sensor
●
Replace the indoor intake air temperature
sensor
●
Detect in indoor unit PCB
●
Replace the indoor unit PCB
For safety reason and to prevent component
breakdown, always switch off the power
before remove and connect the component.
Check the connector connection:
●
Plug out connector from the indoor unit PCB
●
Measure the resistance of the indoor pipe temperature
sensor
Is the connector connection normal?
●
Connector poor contact
●
Correct the connection
YES
NO
Is the measured resistance of the indoor intake air
temperature sensor matches the value specified in its
characteristic chart?
NO
YES
Caution