15.
Power Monitor Display
16.
Remote Control Signal Receiving Sound ON/OFF
17.
Indoor Power Relay Control
Power Monitor LED lights on when the compressor is in operation. The number of the LED lights on is in accordance to the
compressor operating frequency.
Model Display A A, B A, B, C A, B, C, D A, B, C, D, E
Cooling & Soft Dry
Indication Frequency 15 ~ 26 31 ~ 33 36 ~ 40 43 ~ 46 51 ~ 64
(Hz)
CS-G95KE
Heating Indication
Frequency (Hz)
15 ~ 26 31 ~ 40 43 ~ 58 63 ~ 64 71 ~ 99
Cooling & Soft Dry
Indication Frequency 15 ~ 27 31 ~ 36 44 ~ 49 58 ~ 64 71 ~ 92
CS-G125KE (Hz)
Heating Indication
Frequency (Hz)
15 ~ 27 31 ~ 44 58 ~ 79 83 ~ 86 91 ~ 115
Press the Auto button (at indoor unit) for 16 seconds or < 21 seconds. Beep”“beep”“beep”“beep will be heard at 16th second.
Remove the back cover of Remote Control, short the diagnosis (
) terminals at the back of remote control to switch to
Remote Control signal receiving sound ON/OFF mode. One beep will be heard*. Then, press the Auto button once again,
beep sound will be heard. The Remote Control signal receiving sound has been turned off.
Repeat the above procedure or reset the main power supply to switch on the remote control signal receiving sound.
*Ifbeep”“beep sound is heard and E1 or E2 is displayed, the setting has been switched to H14 diagnosis mode.
Refer Servicing Information for more details.
The power relay turns on when one of the indoor LED lights on.
The power relay turns off when all of the indoor LEDs lights off.
When the air conditioner is stopped during operation, the power relay stays ON for 3 minutes.
The power relay will turn off if a sudden power failure occurs
0.05 second. The power relay will turn on again after 3-4 minutes
(Refer AUTO RESTART CONTROL). It will start with the previous operation condition before the power failure.
41