17.4.21. F95 (Cooling High Pressure Abnormality)
Malfunction Decision Conditions
During operation of cooling, when outdoor unit heat exchanger high temperature data (61C) is detected by the outdoor pipe
temperature sensor.
Malfunction Caused
Air short circuit at indoor unit
Dust accumulation on the indoor unit heat exchanger
2/3 way valve closed
Faulty outdoor unit fan motor
Excessive refrigerant
Clogged expansion valve or strainer
Faulty outdoor pipe temperature sensor
Faulty outdoor unit PCB
Troubleshooting