62
During operation mode judgment, indoor fan motor (with speed of Lo-) and outdoor fan motor are running for 30
seconds to detect the indoor intake and outdoor air temperature. The operation mode is decided based on below
chart.
13°C
0°C
28°C19°C
+3.5K
-3.5K
Heating Mode
Dry Mode
Cooling Mode
(Intake air 36°C)
- Temperature setting on
the remote control
Intake air
temperature
Overview of Mode Determination
Dry
Heating
Cooling
Outdoor
temperature
Every 30 minutes, the indoor and outdoor temperature is judged.
The Auto Operation Mode shifting will take place whenever operation mode changed from Cooling/Dry to Heating or
vice versa.
14.1.6 Emergency Operation
Emergency operation can be set by pressed “Auto OFF/ON” button and operate in auto operation at the setting
temperature 25°C.