71
Remaining time appear on the remote control displays for the remaining time every hour. When the time is up the
remaining time display will disappear.
If change the remote control setting temperature during the sleep operation, you can correct the set temperature
during the next sleep operation (up to ± 1°C by pressing “date and time” button (5 seconds or more).
During cooling operation and set to the sleep mode, it will make the cooling and dehumidifying operation.
Temperature Shift
Status 1 Status 2 Status 3 Status 4
Set temperature (°C)
Cooling / Dry 0 +1 +1 +1
Heating 0 -1 -1 -1
o Sleep operation stop condition
Reached delay time.
Pressed sleep button to cancel.
Unit is OFF.
14.8 Auto Restart Control
When the power supply is cut off during the operation of air conditioner, the compressor will re-operate within
three to four minutes (various period of protection control is programmed) after power supply resumes.
The type control is not applicable during ON/OFF Timer setting, Sleep Timer Setting or when there is an
abnormality.
When the power supply resumes, the vertical louver does not closed. Press the “STOP” button if want close the
vertical louver.