86
15. Protection Control
15.1 Protection Control for All Operations
15.1.1 Restart Control (Time Delay Safety Control)
The Compressor will not turn on within 3 minutes from the moment operation stops, although the unit is turned on
again by pressing OFF/ON button at remote control within this period.
This control is not applicable if the power supply is cut off and on again.
This phenomenon is to balance the pressure inside the refrigerant cycle.
15.1.2 Total Running Current
1 When the outdoor unit total running current (AC) exceeds X value, the frequency instructed for compressor
operation will be decreased.
2 If the running current does not exceed X value for 10 seconds, the frequency instructed will be increased.
3 However, if total outdoor unit running current exceeds Y value, compressor will be stopped immediately for
3 minutes.
Model VZ9SKE VZ12SKE
Hz 50 50
Operation Mode X (A) Y (A) X (A) Y (A)
Cooling (A) 6.93 17.2 7.99 17.2
Cooling (B) 5.65 17.2 6.63 17.2
Cooling (C) 4.53 17.2 5.45 17.2
Heating 14.17 17.2 14.17 17.2
4 The first 30 minutes of cooling operation, (A) will be applied.
Outdoor temperature range
Outdoor temperature
Range C
Range B
Range A
39°C
37°C
39 + 1°C
37 + 1°C
Cooling
Maximum Current Limit
Outdoor temperature range
Outdoor temperature
Max Current limited
No limit
6°C
2°C
8°C
4°C
Heating