differences for twin- and triple-type systems.
 
Equivalent length 
 
L + la + lb + lc 
 
Within 50 m 
 
Branch pipe 
diameter 
 
la, lb, (lc) 
 
Within 15 m 
 
Branch pipe 
difference 
 
la - lb, lb - (lc), la - (lc) 
 
Within 10 m 
 
Height difference 
 
H1 
 
Within 30 
m 
 
Height difference between 
indoor units 
 
H2 
 
Within 1 m 
 Note: 
1. Use the main pipe to gain any rise or fall required for the pipes.
2. The number of bends should be 8 or less in a single system (L + 
la, L + lb, L + lc), and 15 or less overall.
3. Branch pipes should be position horizontally.
- The branch pipe shoud be horizontal to or perpendicular to the 
indoor unit.
20.3. Refrigerant charging
- For twin and triple-type systems / The pipe length is the total of the 
branch pipe (L) and the junction pipes (la   lb   lc in order from 
the thickest diameter). At the point where the pipe length exceeds 
30 m, determine the amount of refrigerant for the remaining liquid-