Model Cooling capacities are based on 
conditions below.
CS-
A50BB4P 
Cooling 
capacity 
14.0 kW
 
3 phase, 50Hz, 400V / Indoor 
temperature 27°C D.B. 19°C W.B. / 
Outdoor temperature 35°C D.B. / 
Standard air volume 31m
3
/min 
Entering Temperature Air Entering 
Condenser (°C D.B.)
Air 25 30 35 40 43
Temperature TC TC TC TC TC
D.B. W.B. kW kW kW kW kW
17 14.5 13.5 12.7 12.0 11.4
27 19 15.3 14.6 14.0 13.0 12.3
22 16.3 15.6 15.0 14.3 13.4
Entering Temperature Air Entering 
Condenser (°C D.B.)
Air 25 30 35 40 43
Temperature IPT IPT IPT IPT IPT
D.B. W.B. kW kW kW kW kW
17 3.98 4.34 4.74 5.15 5.46
27 19 4.26 4.64 4.99 5.42 5.75
22 4.60 5.01 5.39 5.80 6.15
94