Loading...
ITEM / MODEL
Indoor Unit Outdoor unit
Main Body CS-A50BD2P CU-A50BBP8
Cooling Capacity kW 14.50
(BTU/h) (49,400)
Heating Capacity kW 15.70
(BTU/h) (53,500)
Refrigerant Charge-less m 30
Standard Air Volume for High
Medium and Low Speed
m
3
/min
Hi 45 Hi 86
cfm Hi 1589 3036
External Static Pressure mmAq Hi 10 Me 5 Lo 0 -
Pa Hi 98 Me 49 Lo 0
Air Inlet Backward Suction Rear sided Suction
Air Outlet Front blow-out Front blow-out
Outside Dimension (H x W x D) mm 360 x (1000 + 10) x 650 1220 x 1100 x 320
Net Weight kg (lbs) 56 (123) 116 (256)
Piping
Connection
Refrigerant
Gas mm (inch) O.D Ø 19.05 (3/4) Flared Type
Liquid mm (inch) O.D Ø 9.52 (3/8) Flared Type
Drain mm Female screw (PT1) I.DØ 20 x 1
Compressor
Type, Number of Set - Hermetic-1 (Scroll), 1
Starting Method - Direct on-line starting
Motor Type - 2-pole 3-phase induction
motor
Input kW - Cool/Heat 4.56/4.54
Rated
Output
kW - 4.1
35