/ / / Equivalent Length = actual pipe length + / number of elbow x ELE + number of oil / trap x ELO / ELE: equivalent length of elbow. / ELO:
equivalent length of oil trap.
10.2. REFRIGERANT ADDITIONAL CHARGE
- The piping length exceeds 30 metres. / APPLICABLE FOR ALL MODELS
Before shipment, this air conditioner is filled with the rated amount of refrigerant subject to 30m
piping length. (The rated amount of refrigerant is indicated on the name plate.) But when the
piping length exceeds 30m, additional charge is required according to the following table.
For other pipe length of other installation multiply / by the following correction factor to determine the revised cooling capacity. / / (Heating)
110