2. When defrosting is complete
1. Start / Hot start control commences when defrosting is complete.
2. Operation / “PREHEAT” appears on the remote control display. (Other displays remain
unchanged.) / At the indoor unit, the indoor unit fan stops. In addition, during hot starting, the
louvre stays at the horizontal / position (angle 0~).
3. Cancelling / Hot starting is cancelled when the temperature detected by the indoor unit pipe
temperature sensor is 18~C / or higher, or after a maximum 1 minute has passed since defrosting
was completed. / After cancellation, the “PREHEAT” display on the remote control disappears
and the louvre operation / returns to the previous setting. / (However, the indoor unit fan operates
at LOW speed for 2 minutes after cancellation, and then returns to / the previous setting.) / <
When hot start operation is cancelled by temperature >