1. Start / Carried out when the compressor switches from on to off (when the remote control unit is
used to stop operation)
2. Operation / The outdoor unit fan runs at SUPER HI speed for approximately 60 seconds and then
stops.
26.12. Discharge temperature control
1. Operation / When the discharge temperature sensor detects a temperature of 100~C or higher
during cooling mode operation, the liquid bypass valve is turned on.
2. Cancelling / When the discharge temperature sensor detects a temperature of 70~C or lower, the
liquid bypass valve is turned off.
26.13. Emergency operation
When the emergency operation switch (DSW1) on the outdoor unit printed circuit board is set to the emergency setting, then emergency
operation is enabled. This allows normal operation to continue, with all abnormalities other than a discharge temperature abnormality, high
pressure abnormality or overcurrent abnormality being ignored.
26.14. DIP switch settings
- Indoor unit printed circuit board (DSW1)