Important
:
The address for the Twin/Triple
control cannot be reset, using the
above mentioned procedure.
2. Manual address setting (by dip-switch DSW1) / When setting the
address manually, set the dip-switch of the PC board of the indoor
unit as follows:
3. Manual address setting (by dip-switch DSW1) / When setting the
address manually, set the dip-switch of the PC board in the indoor
unit as follows:
Procedures of deleting memory for twin/triple control system
1. Switch off the main power supply.
2. Set the No. 8 pin of dip switch (DSW1) at the indoor unit’s P.C.
board to “ON” position.
3. Switch on the main power supply for a minute and then turn it off.
4. Set the No. 8 pin of dip switch (DSW1) to “OFF” position.
Procedures of deleting memory for group control system
1. Switch off the main power supply.
2. Set the No. 1 until No. 4 pin of dip switch (DSW1) at the indoor
unit’s P.C. board to “ON” position. / (Make sure No. 8 pin of dip
switch (DSW1) is at “OFF” position)
3. Switch on the main power supply for a minute and then turn it off.
4. Set the No. 1 pin until No. 4 pin of dip switch (DSW1) to “OFF”
132