100
14.9 Auto Restart Control
When the power supply is cut off during the operation of air conditioner, the compressor will re-operate within
three to four minutes (there are 10 patterns between 2 minutes 58 seconds and 3 minutes 52 seconds to be
selected randomly) after power supply resumes.
This type of control is not applicable during ON/OFF Timer setting.
This control can be omitted by open the circuit of JP1 at indoor unit printed circuit board.
14.10 Indication Panel
LED POWER TIMER iAUTO-X Economy
Color Green Orange Orange Orange
Light ON Operation ON Timer Setting ON iAUTO-X Mode ON Economy ON
Light OFF Operation OFF Timer Setting OFF iAUTO-X Mode OFF Economy OFF
Note:
If POWER LED is blinking, the possible operation of the unit are Hot Start, during Deice operation, operation
mode judgment, or ON timer sampling.
If Timer LED is blinking, there is an abnormality operation occurs.
14.11 Economy Mode Operation
This operation is use to reduce electrical power consumption by adjusting the set temperature.
Economy operation starts when the Economy button is pressed during cooling or dry operation.
During Cooling/Dry economy operation, target setting temperature will be adjusted by +2°C. Internal setting
temperature limit shift to maximum 35°C (maximum 33°C + 2°C Economy shift).
During Economy operation, all indicators includes Economy indicator will be dimmed. The brightness level is
equivalent to indicator dim function.
Powerful, Quiet and Economy could not be operated at the same time. The unit will follow the latest setting of
these three operations.
The Economy operation stops when:
1 iAUTO-X button is pressed.
2 POWERFUL/QUIET button is pressed.
3 Operation OFF.
4 Received Economy signal from remote control again.
5 Received either Powerful or Quiet operation signal from remote control.
14.12 HA Terminal (HAJEM-A)
Enable digital connection from indoor unit to external devices.
Control items:
1 Start/stop input.
2 Start/stop signal output.
Condition
1 1-2 (Pulse input): Unit ON/OFF condition switching with a pulse signal.
(1 pulse signal: shortage status 200~300msec)
2 3-4 (Static output): 5V output during the unit ON. No output at OFF.
ON/OFF input
(Pin 1-2)
Monitor output
(Pin 1-2)
ON ON
OFF
Unit condition
200~300msec
+5V