162
20. Service Data
Service data provided are based on the air conditioner running under rated frequency during forced cooling / forced
heating mode.
20.1 Cool Mode Outdoor Air Temperature Characteristic
Condition
- Indoor room temperature: 27°C DryBulb/19°C Wet Bulb
- Unit setting: Standard piping length, forced cooling at 16°C, Hi fan
- Compressor frequency: Rated for cooling operation
- Piping length: 5m
- Voltage: 230/240V
20.1.1 CS-RZ25TKR CU-RZ25TKR
Outdoor
Temperature (°C)
Indoor Discharge
Air Temperature
(°C)
16 15.51
25 15.04
35 16.41
46 20.07
Outdoor
Temperature (°C)
Current (A)
230V 240V
16 2.07 1.97
25 2.53 2.43
35 3.20 3.10
46 3.94 3.84
Outdoor
Temperature (°C)
Gas Side Piping
Pressure
(MPa) (Psi)
16 0.812 118.000
25 0.949 138.000
35 1.094 159.000
46 1.270 184.000
14.000
15.000
16.000
17.000
18.000
19.000
20.000
21.000
16 18 20 22 24 26 28 30 32 34 36 38 40 42 44 46
Indoor Discharge
Air Temperature
(°C)
Outdoor Air Temperature (°C)
230
240
1.500
2.000
2.500
3.000
3.500
4.000
16 18 20 22 24 26 28 30 32 34 36 38 40 42 44 46
Current
(A)
Outdoor Air Temperature (°C)
0.800
0.900
1.000
1.100
1.200
1.300
16 18 20 22 24 26 28 30 32 34 36 38 40 42 44 46
Gas Side Piping
Pressure (MPa)
Outdoor Air Temperature (°C)
116.000
131.000
145.000
160.000
174.000
189.000
Gas Side Piping
Pressure (Psi)