174
20.3 Piping Length Correction Factor
The characteristic of the unit has to be corrected in accordance with the piping length.
20.3.1 CS-RZ25TKR CU-RZ25TKR CS-RZ35TKR CU-RZ35TKR
Note: The graphs show the factor after added right amount of additional
refrigerant.
Cooling Capacity
3 1.001
5 1.0000
7.5 0.9793
15 0.9107
20 0.9085
Heating Capacity
3 1.006
5 1.0000
7.5 0.9979
15 0.9773
20 0.9675
0.900
0.920
0.940
0.960
0.980
1.000
1.020
34567891011121314151617181920
Cooling Capacity
Correction Factor
Piping Length (m)
0.960
0.970
0.980
0.990
1.000
1.010
34567891011121314151617181920
Heating Capacity
Correction Factor
Piping Length (m)