or Main Unit (Touch Control Panel) setting.
8.1.1. Manual Setting of Fan Speed
- Basic Fan Speed can be manually adjusted (Lo, Med or Hi) by
using the Fan Speed Selection Button/Pad at Remote Control or
Main Unit (Touch Control Panel).
8.2. Cooling Mode Operation
- Cooling in operation according to Remote Control or Main Unit
(Touch Control Panel) setting.
8.2.1. Time Delay Safety Control (3 minute)
- When the compressor is stopped by Operation Switch at the
Remote Control or Main Unit (Touch Control Panel), it restart after
3 minutes when the Operation Switch at the Remote Control or
Main Unit (Touch Control Panel) is turned ON.
- When the setting temperature is reached during cooling operation,
the compressor stops and it will not start for 3 minutes.
- Protection of compressor to balance the pressure in the
refrigeration cycle for 3 minutes.
8.2.2. 7 minutes Time Saved Control
- The compressor will start automatically if it has stopped for 7
minutes even if the room temperature is between the compressor
ON temperature and OFF temperature.
8.2.3. Starting Current Control
- When the compressor and fan motor are simultaneously started,
the fan motor will operate 1.6 seconds later.
8.2.4. Freeze Prevention Control
- If the temperature of the indoor heat exchanger falls continuously
below 34°F for 3 minutes or more, the compressor turns off to
protect the heat exchanger from freezing. The fan speed setting
remains the same.
- Compressor restarts when the heat exchanger temperature rises to
54°F (Recovery).
*3 minutes waiting of Time Delay Safety Control is valid for
Cooling Operation.