8.2.5. Compressor Reverse Rotation Protection Control
- If the compressor is operating continuously for 5 minutes or longer
and the temperature difference between intake air and heat
exchanger is 4.5°F or less for 2 minutes, compressor will stop and
restart automatically (Time Delay Safety Control is valid).
8.2.6. Cooling Operation Time Diagram