1
1-293
* If multiple indoor units are used, also refer to section āSystem Controlā.
Type U1, T2, F1, N1 and Y2
Caution
Test Run Procedure
This unit may be used in a single-type refrigerant system where 1 outdoor unit is connected to 1 indoor
unit, and also in a system where 1 outdoor unit is connected to multiple indoor units (maximum 2).
The indoor and outdoor unit control PCB utilizes a semiconductor memory element (EEPROM).
The settings required for operation were made at the time of shipment.
Only the correct combinations of indoor and outdoor units can be used.
This test run section describes primarily the procedure when using the wired remote controller.
YES
YES
YES
NO
NO
NO
Recheck the items to check before the test run.
Check the combination (wiring) of indoor and outdoor units.
See section āSystem Controlā
See section āItems to Check
Before the Test Runā
Is system āsingle-typeā?
(1 indoor unit is connected
to 1 outdoor unit and remote
controller)
Is group control with multiple outdoor units used?
Turn ON the indoor and outdoor power.
Indicate (mark) the combination number.
Automatic
address
setting
Set the remote controller to ātest runā.
See section āTest Run Using
the Remote Controllerā
See section āIndicating
(marking) the indoor
and outdoor unit
combination numberā
Can
operation be
started?
Return the remote controller to normal control.
Turn ON the indoor
and outdoor power.
(Automatic Address Setting)
See section āSetting the outdoor
unit System Addressā
Set the outdoor
unit system
address.
Use the remote
controller to
perform automatic
address setting.
Refer to āTable of Self-
Diagnostic Functionsā
to check the system.
In addition, refer to
8-8-1 to 5 and correct
any items that need to
be corrected.
Note: Check the indoor-side drainage.
(*1) Required for simultaneous-operation
multi systems and for group control.
(*1)
See section āAutomatic address
setting using the remote controllerā
SM830231-02īSingleī꬧å·.indbīīī293SM830231-02īSingleī꬧å·.indbīīī293 2014/09/19īīī13:21:472014/09/19īīī13:21:47