4-18
4
2) Maximum and Minimum Frequency Control
* There is a case in which the frequency set at maximum and minimum may sometimes decrease in accordance
with ambient temperature and indoor loads.
3) Current Release Control
125PEY1E8
125PEY1E5
60PE1E5A
71PE1E8A
71PE1E5A
125PE1E8A
125PE1E5A
140PE1E8A
140PE1E5A
100PE1E8A
100PE1E5A
PE PEY
100PEY1E8
100PEY1E5
Maximum Frequency (Hz)
Cooling
Heating
70.0
85.0
15.0
15.0
70.0
85.0
15.0
15.0
55.0
90.0
15.0
15.0
65.0
95.0
15.0
15.0
75.0
100.0
15.0
15.0
70.0
99.0
15.0
15.0
59.0
80.0
15.0
15.0
140PEY1E8
75.0
95.0
15.0
15.0
Minimum Frequency (Hz)
Cooling
Heating
PE PEY
Is (A)
Cooling
Heating
71PE1E5A
14.5
18.0
71PE1E8A
—
6.0
7.0
60PE1E5A
14.5
18.0
—
—
100PE1E5A
24.0
24.0
100PE1E8A
8.0
8.5
125PE1E5A
26.0
26.0
125PE1E8A
8.6
9.5
140PE1E5A
27.0
28.0
140PE1E8A
9.0
10.5
100PEY1E5
24.0
24.0
100PEY1E8
8.0
8.5
125PEY1E5
27.0
27.0
125PEY1E8
140PEY1E8
9.0
9.5
—
—
—
9.0
9.5
Is (A)
Cooling
Heating
1) Indoor Air Temperature Control
By the control method, not only the thermostat is switched on and off, as explained section ā€œ4-12-3ā€.
Indoor Air Temperature Control ", but also the frequency of the compressor's inverter is controlled in
accordance with T and fluctuations in indoor air temperature. Inverter frequency is controlled as follows:
ī˜‚ Maximum and Minimum Frequency
When T is high (not yet reached the temperature set
with the remote controller).
Controlled so that the inverter frequency is increased.
When
T is low (approximately +1.0 or less in the
cooling mode or approximately -1.0 or more in the
heating mode).
Controlled so that the inverter frequency is decreased
or kept.
The compressor's inverter frequency is controlled in accordance with the model and operation mode.
The maximum and minimum frequencies for each model are shown in the table below.
* There are cases in which frequency is limited with other control functions depending on operational conditions,
so operations are not always carried out in accordance with the maximum frequencies listed below.
The inverter frequency is controlled so that the current value for the inverter compressor is less than the figure
listed in the table below in order to prevent abnormal increases in the inverter circuit located within the outdoor
unit's electrical box.
Current release control with primary current : The limited values are modified in accordance with ambient
temperature.
SM830231-02Singleī™€ę¬§å·ž.indb18SM830231-02Singleī™€ę¬§å·ž.indb18 2014/09/0921:15:232014/09/0921:15:23

Table of Contents

Other manuals for Panasonic CZ-KPY3A series

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Panasonic CZ-KPY3A series and is the answer not in the manual?

Panasonic CZ-KPY3A series Specifications

General IconGeneral
BrandPanasonic
ModelCZ-KPY3A series
CategoryAir Conditioner
LanguageEnglish

Related product manuals