1-7-2
1
Graph of capacity change characteristics resulting from tubing length and elevation difference
0
98
96
94
92 90 88 86 84
%
100
10 20 30 40 50 60 70 80 90
Elevation difference (m)
<Cooling>
Base capacity
change rate
Equivalent length (m)
(Performance correction coefficients by elevation difference of refrigerant tube length [performance change rate ÷ 100] is
calculated by the following line map.)
0
99
98
97 96 95 94 93 92 91 90
%
100
-30
-10
0
10
20
30
5010 20 30 40 70 80 9060
-20
-30
-10
0
10
20
30
-20
Elevation difference (m)
Equivalent length (m)
<Heating>
<Cooling>
<Heating>
Base capacity
change rate
0
98
96
94
92 90 88 86
%
100
10 20 30 40 50 60 70 80
Elevation difference (m)
<Cooling>
Base capacity
change rate
Equivalent length (m)
0
99
98
97 96 95 94 93 92 91
%
100
-30
-10
0
10
20
30
5010 20 30 40 70 8060
-20
-30
-10
0
10
20
30
-20
Elevation difference (m)
Equivalent length (m)
<Heating>
Base capacity
change rate
0
98
96
94
92 90
%
100
10 20 30 40 50 60
Elevation difference (m)
Base capacity
change rate
Equivalent length (m)
0
99
98
97 96 95 94 93
%
100
-30
-10
0
10
20
30
50 6010 20 30 40
-20
-30
-10
0
10
20
30
-20
Elevation difference (m)
Equivalent length (m)
Base capacity
change rate
U-200PZH2E8 (For 50 Hz)
Type E3
Type U2
U-250PZH2E8 (For 50 Hz)
Type E3, Type U2
*The positive side for the elevation difference indicates that the outdoor unit is installed at a higher position than the indoor units.
The negative side indicates the opposite.