MEWTOCOL
Modbus
Function
Code
Data Item Data
DT00114 03/06/10H 000EH SV1 Set value, Decimal point ignored
DT00115 03/06/10H 000FH SV2 Set value, Decimal point ignored
DT00116 03/06/10H 0010H SV3 Set value, Decimal point ignored
DT00117 03/06/10H 0011H SV4 Set value, Decimal point ignored
DT00118 03/06/10H 0012H EV1 alarm value (*1) Set value, Decimal point ignored
DT00119 03/06/10H 0013H EV1 high limit alarm value (*1) Set value, Decimal point ignored
DT00120 03/06/10H 0014H EV2 alarm value (*1) Set value, Decimal point ignored
DT00121 03/06/10H 0015H EV2 high limit alarm value (*1) Set value, Decimal point ignored
DT00122 03/06/10H 0016H Reserved (*2)
: : : :
DT00129 03/06/10H 001DH Reserved (*2)
DT00130 03/06/10H 001EH Loop break alarm time Set value
DT00131 03/06/10H 001FH Loop break alarm span Set value, Decimal point ignored
DT00132 03/06/10H 0020H Reserved (*2)
: : : :
DT00135 03/06/10H 0023H Reserved (*2)
DT00136 03/06/10H 0024H EV1 alarm value 0
Enabled/Disabled
0000H : Disabled
0001H : Enabled
DT00137 03/06/10H 0025H EV1 alarm hysteresis Set value, Decimal point ignored
DT00138 03/06/10H 0026H EV1 alarm delay time Set value
DT00139 03/06/10H 0027H EV1 alarm
Energized/De-energized
0000H : Energized
0001H : De-energized
DT00140 03/06/10H 0028H EV2 alarm value 0
Enabled/Disabled
0000H : Disabled
0001H : Enabled
DT00141 03/06/10H 0029H EV2 alarm hysteresis Set value, Decimal point ignored
DT00142 03/06/10H 002AH EV2 alarm delay time Set value
DT00143 03/06/10H 002BH EV2 alarm
Energized/De-energized
0000H : Energized
0001H : De-energized
DT00144 03/06/10H 002CH Reserved (*2)
: : : :
DT00159 03/06/10H 003BH Reserved (*2)
DT00160 03/06/10H 003CH OUT1 proportional band Set value, Decimal point ignored
DT00161 03/06/10H 003DH Integral time
Set value
DT00162 03/06/10H 003EH Derivative time
Set value
DT00163 03/06/10H 003FH ARW
Set value
DT00164 03/06/10H 0040H Manual reset Set value, Decimal point ignored
DT00165 03/06/10H 0041H OUT1 proportional cycle Set value
DT00166 03/06/10H 0042H OUT1 ON/OFF hysteresis Set value, Decimal point ignored
DT00167 03/06/10H 0043H OUT1 high limit
Set value
DT00168 03/06/10H 0044H OUT1 low limit
Set value
DT00169 03/06/10H 0045H OUT1 rate-of-change
Set value
DT00170 03/06/10H 0046H OUT2 cooling method 0000H : Air cooling
0001H : Oil cooling
0002H : Water cooling
DT00171 03/06/10H 0047H OUT2 proportional band Set value, Decimal point ignored
DT00172 03/06/10H 0048H OUT2 proportional cycle Set value
DT00173 03/06/10H 0049H OUT2 ON/OFF hysteresis Set value, Decimal point ignored
DT00174 03/06/10H 004AH OUT2 high limit
Set value
DT00175 03/06/10H 004BH OUT2 low limit
Set value
DT00176 03/06/10H 004CH Overlap band/Dead band Set value, Decimal point ignored