6.1.5 Contact No.
Contact No. Read/Write Contents of Data Data Section
R0000 R/W EV1 alarm Energized/De-energized 0000H : Energized (OFF)
0001H : De-energized (ON)
R0001 R/W
EV1 alarm value 0 Enabled/Disabled
0000H : Disabled (OFF)
0001H : Enabled (ON)
R0002 R/W EV2 alarm Energized/De-energized 0000H : Energized (OFF)
0001H : De-energized (ON)
R0003 R/W
EV2 alarm value 0 Enabled/Disabled
0000H : Disabled (OFF)
0001H : Enabled (ON)
R0004 R/W Direct/Reverse action 0000H : Reverse action (OFF)
0001H : Direct action (ON)
R0005 R/W SV Rise/Fall rate start type 0000H : SV start (OFF)
0001H : PV start (ON)
R0006 R/W
Output status when input errors
occur
0000H : Output OFF(OFF)
0001H : Output ON(ON)
R0007 R/W Auto/Manual after power interruption 0000H : Automatic control (OFF)
0001H : Manual control (ON)
R0008 R/W Step time unit 0000H : Hours:Minutes (OFF)
0001H : Minutes:Seconds (ON)
R0009 R/W Control method 0000H : Usual PID (OFF)
0001H : 2DOF PID (ON)
R000A R/W Reserved (*2) Always 0000H
R000B R/W
Control output OFF function,
Auto/Manual control,
Program control RUN/STOP
When Control output OFF function is
selected:
0000H: Control output ON (OFF)
0001H: Control output OFF (ON)
When Auto/Manual control is
selected:
0000H: Automatic control (OFF)
0001H: Manual control (ON)
When Program control is selected:
0000H: Program control STOP
(OFF)
0001H: Program control RUN
(ON)
R000C R/W Program control Holding/Not holding 0000H : Not holding (OFF)
0001H : Holding (ON)
R000D W Program control Advance (*5) 0001H : Advance Perform (ON)
R000E R/W Controller/Converter 0000H : Controller (OFF)
0001H : Converter (ON)
R000F R/W
EV1 output by communication
command
0000H : OFF
0001H : ON
R0010 R/W
EV2 output by communication
command
0000H : OFF
0001H : ON
R0011 R/W AT/Auto-reset Perform/Cancel 0000H : AT/Auto-reset Cancel (OFF)
0001H : AT/Auto-reset Perform (ON)
R0012 R/W AT on startup Perform/Cancel 0000H : AT on startup Cancel(OFF)
0001H : AT on startup Perform(ON)
R0013 W
Key operation change flag
clearing (*7)
0001H : Clear key operation change
flag (ON)
R0014 R/W Reserved (*2)
Always 0000H
R0015 R/W Reserved (*2)
Always 0000H
R0016 R/W Reserved (*2)
Always 0000H