Contact No. Read/Write Contents of Data Data Section
R0061 R EV2 output Enabled/Disabled 0000H : Disabled (OFF)
0001H : Enabled (ON)
R0062 R Reserved (*2)
Always 0000H
R0063 R Reserved (*2)
Always 0000H
R0064 R Reserved (*2)
Always 0000H
R0065 R Reserved (*2)
Always 0000H
R0066 R Reserved (*2)
Always 0000H
R0067 R Communication function
Enabled/Disabled
0000H : Disabled (OFF)
0001H : Enabled (ON)
R0068 R Heating/Cooling control function
Disabled/Enabled
0000H : Disabled (OFF)
0001H : Enabled (ON)
R0069 R Reserved (*2) Always 0000H
R006A R Reserved (*2) Always 0000H
R006B R Reserved (*2)
Always 0000H
R006C R Reserved (*2)
Always 0000H
R006D R Reserved (*2)
Always 0000H
R006E R Reserved (*2)
Always 0000H
R006F R Reserved (*2)
Always 0000H
R0070 R Unit model: AKT9R 0001H : Specified model
R0071 R Unit model: AKT8R 0001H : Specified model
R0072 R Reserved (*2) Always 0000H
R0073 R Unit model: AKT4R 0001H : Specified model
R0074 R Reserved (*2)
Always 0000H
R0075 R Reserved (*2)
Always 0000H
R0076 R OUT1 output type: Relay contact
output
0001H : Specified model
R0077 R OUT1 output type: Non-contact
voltage output (for SSR drive)
0001H : Specified model
R0078 R OUT1 output type: Direct current
output
0001H : Specified model
R0079 R OUT2 output type : Relay contact
output
0001H : Specified model
R007A R Reserved (*2) Always 0000H
: : : :
R009F R Reserved (*2) Always 0000H
R/W: Both Read and Write can be executed.
R: Read can be executed. If Write is executed, data will be discarded, and acknowledgement will be returned.
If Data larger than Contact No. R0100 is read or written, Error code 61H will be returned.
If Data larger than DT10000 is read or written, Error code 61H will be returned.
(*1) If any action is changed in [Event output EV1 allocation] or in [Event output EV2 allocation], EV1 alarm value and EV2 alarm value, etc. will
revert to factory default value.
For the items to be initialized: Refer to Section “6.6 Items to Be Initialized by Changing Settings” (p.55).
(*2) If reserved items and reserved Contact No. are read, acknowledgement will be returned (but data is 0).
If they are written, data will be discarded, and acknowledgement will be returned.
(*3) If ‘Not used’ items are read or written, the following data will be returned depending on the communication protocol.
For MEWTOCOL, if ‘Not used items are read, acknowledgement will be returned (but data is 0). If they are written, data will be discarded, and
acknowledgement will be returned.
For Modbus, Exception code 2 (02H) will be returned.
(*4) For Manual control MV, if the following are written, Error code 61H (MEWTOCOL) or Exception code 3 (03H, Modbus) will be returned.
When control action is ON/OFF control, and if any items except OUT1 low limit and OUT1 high limit values are written.
When Heating side (of Heating/Cooling control) is in ON/OFF control, and if any items - except Heating side OUT1 low limit/OUT1 high limit value,
and Cooling side OUT2 low limit/OUT2 high limit value - are written.
When Cooling side (of Heating/Cooling control) is in ON/OFF control, and if any items - except Heating side OUT1 low limit/OUT1 high limit value,
and Cooling side OUT2 low limit/OUT2 high limit value - are written.