Over-load warning
release level
Sets the threshold value for releasing
the warning when the load factor
decreases from the state when the
overload warning is occurring.
Sets with the overload load factor.
If 0 is set, overload warning detection
is performed under conventional
conditions (85% of overload protection
level).
In addition, if other than “Pr6.96 <=
Pr6.95 < (Overload level)” is set,
overload warning detection is
performed under conventional
conditions (85% of overload protection
level).
Function expansion
setup 3
-2147483648
to
2147483647
Set various functions on a bit basis.
4.5.4
5.2.15
6.2
6.8
Ether CAT
Enables/Disables quadrant
projection compensation function
extended.
0: Disabled
1: Enabled
* To set the compensation
amount of quadrant projection
by inversion direction when the
direction of the velocity has
changed, set Pr6.97 bit0 to 1.
Deterioration diagnosis warning
function:
0: Disabled
1: Enabled
Expansion of Allowable motor
operating range abnormal
protection:
0: Disabled
1: Enabled
For manufacture use.
Permanently set at 0.
Extension of the subject control
mode for 607Fh/687Fh (Max
profile velocity).
0: standard specifications
(pp,hm,ip,pv)
1: expansion specification
(pp,hm,ip,pv,tq,cst)
For manufacture use.
Permanently set at 0.
bit 0 is the least significant bit.