If torque saturated is continued
during a preset frequency, Err 16.1
"Torque saturation protection" will
be activated.
The number of times is counted up
every 0.25 ms. For example, when
30000 is set, Err16.1 occurs if the
torque saturation condition
continues for 7.5 seconds.
The count is cleared when the
torque saturation condition is
removed.
When the value set for Pr6.57 is
other than 0, the value set for Pr6.57
is enabled.
Set up the properly according to the
specifications of the host controller.
If the setting is not proper, the
operation is not be guaranteed.