Communication
function extended
setup 3
EX-OUT1 output status setting
when communication is cut off after
establishing EtherCAT
communication.
0: Hold
1: Initialization
For manufacturer’s use
Permanently set at 0.
For manufacturer’s use
Permanently set at 1.
The correction function for
detection delay of latch position.
0: The correction time of both the
latch signal rising edge
detection and the latch signal
falling edge detection is set by
Pr7.09
1: The correction time of the latch
signal rising edge detection is
set by Pr7.09, the correction
time of the latch signal falling
edge detection is set by Pr7.92.
For manufacturer’s use
Permanently set at 0.
Internal value state selection of
objects 60B2h/68B2h (Torque
offset) in servo-off(Fall prevention
function in the event of Servo-ON)
0: Clear
1: Updated with the set value of
60B2h/68B2h
*When this setting value is set to
1, set the value of 60B2h /
68B2h (Torque offset) to a value
smaller than the value of Pr5.11
"Torque setup for emergency
stop".
For manufacturer’s use
Permanently set at 0.
The setting condition of
6041h/6841h
bit12(drive follows command
value).
0: Limiting torque and speed
limit (only cst) is included.
1: Limiting torque and speed
limit (only cst) is not included.
For manufacturer’s use
Permanently set at 1.
Station Alias setup
(high)
Define the higher 8 bits of station alias.
Select the setting origin of a station
alias.
0: RSW(lower)+Pr7.40(higher)
1: SII
2: For manufacturer’s use