4-62
Default: [ ]
Pr5.36
For manufacturer's use
Range Unit Default
Related
control mode
0
Fixedto0.
Pr5.37
*
Modbus connection setting
Range Unit Default
Related
control mode
0 to 2 0 P S T F
To set RS232/RS485 communications protocol.
Setup value
Content
[0] MINASstandardprotocol
1 Modbus-RTU(RS232communications,onlyfor1:1)
2 Modbus-RTU(RS485communications,1:Ncapable)
Pr5.38
*
Modbus communication setting
Range Unit Default
Related
control mode
0 to 5 0 P S T F
Tosetparity(even,odd,none)andstopbitlength(1bit,2bit)ofModbuscommunications.
Setup value
Content
Setup value
Content
[0]
Even/1bit
3
Odd/2 bit
1
Even/2bit
4
None/1bit
2
Odd/1 bit
5
None/2bit
Pr5.39
Modbusresponsewaitingtime
Range Unit Default
Related
control mode
0 to 10000 ms 0 P S T F
TosetwaitingtimetobeaddedfromthereceiptofModbuscommunicationrequesttillthe
transmission of response data.
Note)Delaytimewillbegeneratedforthecreationofresponsedata,evenifthevalueisset
to0(zero).
Pr5.40
Modbus communication timeout time
Range Unit Default
Related
control mode
0 to 10000 ms 0 P S T F
TosetthetimerequiredtodetectErr.80.0“Modbuscommunicationtimeoutprotection”in
casebroadcastdesignatedModbuscommunicationsfromownspeciedaxishasnotbeen
receivedexceedingthesettime,whilemaintainingthestatewhereModbusexerciserightis
secured.
Err.80.0isnotdetectedwhensetvalueissetto0(zero).
Pr5.41
For manufacturer’s use
Range Unit Default
Related
control mode
0
Plesesxedto0.
1. Details of parameter
[Class 5] Enhancing setting