EasyManua.ls Logo

Panasonic R410A: 5/16 - Insulating the Refrigerant Tubing

Panasonic R410A: 5/16
52 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
30
Unit side
insulator
Insulation tape (white)
(supplied)
Sealer (supplied)
Flare insulator (supplied)
Tube insulator
(not supplied)
Heat resistant
248°F or above
Vinyl clamps (supplied)
Flare nut
Fig. 5-8
Fig. 5-7
5-3. Insulating the Refrigerant Tubing
Tubing Insulation
Thermal insulation must be applied to all unit tubing,
including the distribution joint (purchased separately).
(Fig. 5-7)
* For gas tubing, the insulation material must be heat
resistant to 248°F or above. For other tubing, it must be
heat resistant to 176°F or above.
Insulation material thickness must be 25/64" or greater.
If the conditions inside the ceiling exceed DB 86°F and RH
70%, increase the thickness of the gas tubing insulation
material by 1 step.
Taping the flare nuts
Wind the white insulation tape around the flare nuts at the gas
tube connections. Then cover up the tubing connections with
the flare insulator, and fill the gap at the union with the sup-
plied black insulation tape. Finally, fasten the insulator at both
ends with the supplied vinyl clamps. (Fig. 5-8)
CAUTION
Gas tubing
Liquid tubing
Insulation
Three tubes arranged together
Two tubes arranged together
If the exterior of the outdoor unit
valves has been finished with a
square duct covering, make sure
you allow sufficient space to use
the valves and to allow the panels
to be attached and removed.
Cosmetic
(finishing) tape
Liquid tubing
Gas tubing
Insulation
Balance tubing

Table of Contents

Related product manuals