1-1-13
11
Single-Type
1-1. Unit Specifications
Ducted Type S-100PE1R5B / U-100PZ2R8
INDOOR MODEL S–100PE1R5B – –
PANEL MODEL – – –
OUTDOOR MODEL – U-100PZ2R8 –
Branch pipe MODEL –
Performance test condition ISO13253 / AS/NZS3823.1
Power supply
ø, Hz 1ø 50 Hz 3ø 50 Hz
V – 230 V 240 V – 400 V 415 V Min Max
C
O
O
L
I
N
G
Capacity
kW – 10.0 10.0 – – – 3.0 11.5
BTU/h – 34100 34100 – – – 10200 39200
Current A – 1.72 1.74 – 3.90 3.75 – –
Input power
W – 390 410 – 2.610k 2.590k – –
TOTAL W – – 3.000k 3.000k 850 4.290k
Annual consumption TOTAL kWh *
4
– – 1500 - – –
EER/ AEER/ STAR RATING TOTAL (W/W/-) – – – –
3.33/3.28/-
3.44 3.53 2.68
Power factor % – – – – 97 96 – –
Noise indoor
dB-A (H/M/L) 48/46/44 – – –
Power Level dB 70/68/66 – – –
Noise outdoor
dB-A (H/L) – 52/– – –
Power Level dB – 68/– – –
H
E
A
T
I
N
G
Capacity
kW – 10.0 10.0 – – – 3.0 14.0
BTU/h – 34100 34100 – – – 10200 47800
Current A – 1.72 1.74 – 3.40 3.24 – –
Input power
W – 390 410 – 2.180k 2.160k – –
TOTAL W – – 2.570k 2.570k 855 4.195k
COP/ ACOP/ STAR RATING TOTAL (W/W/-) – – – –
3.89/3.83/-
3.89 3.51 3.34
Power factor % – – – – 93 93 – –
Noise indoor
dB-A (H/M/L) 48/46/44 – – –
Power Level dB 70/68/66 – – –
Noise outdoor
dB-A (H/L) – 52/– – –
Power Level dB – 67/– – –
EXTRA LOW TEMP
Total capacity(kW) / Input power(W) / COP – –
Max Current (A) / Max Input power (W) – 2.0/440 2.1/470 –
9.00/5.80k 9.00/6.05k
–
Starting current (A) / Comp output (W) – – – –
3.90/2.50k 3.75/2.50k
–
Network Impedance (ΩMAX.) – – –
Fan motor output (Indoor/Outdoor) W 275 120 –
Moisture removal volume L/h(Pt/h) 6.0 (12.6) – –
External static pressure Pa - – –
Indoor
Air ow
Cooling m
3
/min (ft
3
/min) 40/35/29 (1413/1236/1024) – – –
Heating m
3
/min (ft
3
/min) 40/35/29 (1413/1236/1024) – – –
Outdoor
Air ow
Cooling m
3
/min (ft
3
/min) – 77.0 (2719) – –
Heating m
3
/min (ft
3
/min) – 70.0 (2472) – –
Refrigerant type / amount
g
(oz) – R32 2.60 k (91.7) –
Product dimension
Height mm(inch) 360 (14–5/32) 996 (39- 7/32) –
Width mm(inch)
1100(+100)
(
43–5/16(+3–15/16))
980 (38-37/64) –
Depth mm(inch) 700 (27–9/16) 370 (14- 9/16) –
Packing dimension
Height mm(inch) 445 1134 (44-41/64) –
Width mm(inch) 1315 1095 (43-7/64) –
Depth mm(inch) 812 529 (20-53/64) –
Weight
(NET) k
g
(lb) 44 90 (199) –
(GROSS) k
g
(lb) 52 98 (216) –
Layers limit (actually) 6(7) 2(3) –
Operation condition
Cool (DBT) 18˚C – 32˚C -10˚C – 43˚C –
Heat (DBT) 16˚C – 30˚C -15˚C – 24˚C –
MAX WORKING PRESSURE HP/LP MPa (bar) 4.15/2.55 (41.5/25.5) –
P
I
P
I
N
G
Pipe diameter mm (inch)
(Liquid)ø9.52(3/8) (Gas)ø15.88(5/8) (Liquid)ø9.52(3/8) (Gas)ø15.88(5/8)
–
Connecting method, Standard length m(ft) ared type, 5.0(16.4) ared type, 5.0(16.4) –
Pipe length range m (ft) 5 ~ 50m (16.4 ~164.0) –
Indoor unit & Outdoor unit height difference m (ft) 15m(OD located lower)/30m(OD located higher) (49.2/98.4) –
Add gas amount
g
/m (oz/ft) 45
g
/m
(0.484) –
Pipe length for additional gas m (ft) 30m (98.4) –
*1 In case it is necessary to indicate the air flow volume in (l/s), the value in (m³/min.) shall be multiplied by 16.7 and rounded down the decimal point.
*2 If the EUROVENT Certified models can be operated under the "extra-low"temperature condition, -7°C dry bulb and -8°C wet-bulb temperatures with rated voltage
230V shall be used.
*3 Network Impedance shall be applicable for EUROPE and CHINA models.
*4 The annual consumption is calculated by multiplying the input power at 230V(400V) by an average of 500 hours per year in cooling mode.
*5 EER and COP classification is at 230V(400V) only in accordance with EU directive 2002/31/EC.
SM830266-00_大洋州向けR32シングルTD&SM.indb 13 18/03/29 10:19:23