1-1. Unit Specifications
Ceiling Type S-60PT2E5B / U-60PZ2R5
INDOOR MODEL S-60PT2E5B – –
PANEL MODEL – – –
OUTDOOR MODEL – U-60PZ2R5 –
Branch pipe MODEL –
Performance test condition ISO5151 / AS/NZS3823.1
Power supply
ø, Hz 1ø 50 Hz 1ø 50 Hz
V – 230 V 240 V – 230 V 240 V Min Max
C
O
O
L
I
N
G
Capacity
kW – 6.0 6.0 – – – 2.0 7.1
BTU/h – 20500 20500 – – – 6800 24200
Current A – 0.41 0.40 – 6.90 6.60 – –
Input power
W – 50 50 – 1.430k 1.430k – –
TOTAL W – – 1.480k 1.480k 300 2.000k
Annual consumption TOTAL kWh *
4
– – 740 – – –
EER/ AEER/ STAR RATING TOTAL (W/W/-) – – – –
4.05/3.90/3
4.05 6.67 3.55
Power factor % – – – – 90 90 – –
Noise indoor
dB-A (H/M/L) 38/34/30 – – –
Power Level dB 56/52/48 – – –
Noise outdoor
dB-A (H/L) – 46/– – –
Power Level dB – 65/– – –
H
E
A
T
I
N
G
Capacity
kW – 6.0 6.0 – – – 1.8 7.6
BTU/h – 20500 20500 – – – 6100 25900
Current A – 0.41 0.40 – 5.80 5.55 – –
Input power
W – 50 50 – 1.200k 1.200k – –
TOTAL W – – 1.250k 1.250k 230 2.300k
COP/ ACOP/ STAR RATING TOTAL (W/W/-) – – – –
4.80/4.59/4.5
4.80 7.83 3.30
Power factor % – – – – 90 90 – –
Noise indoor
dB-A (H/M/L) 38/34/30 – – –
Power Level dB 56/52/48 – – –
Noise outdoor
dB-A (H/L) – 48/– – –
Power Level dB – 66/– – –
EXTRA LOW TEMP
Total capacity(kW) / Input power(W) / COP – –
Max Current (A) / Max Input power (W) –
0.41/50 0.40/50
– 16.4/3.39k
16.4/3.54k
–
Starting current (A) / Comp output (W) – – – – 6.90/1.7k 6.60/1.7k –
Network Impedance (ΩMAX.) – – –
Fan motor output (Indoor/Outdoor) W 74 60 –
Moisture removal volume L/h(Pt/h) 3.4 (7.1) – –
External static pressure Pa – – –
Indoor
Air ow
Cooling m
3
/min (ft
3
/min) 20/17/14.5 (706/600/512) – – –
Heating m
3
/min (ft
3
/min) 20/17/14.5 (706/600/512) – – –
Outdoor
Air ow
Cooling m
3
/min (ft
3
/min) – 45 (1589) – –
Heating m
3
/min (ft
3
/min) – 45 (1589) – –
Refrigerant type / amount
g
(oz) – R32 1.45 k (51.1) –
Product dimension
Height mm(inch) 235 (9-1/4) 695 (27-23/64) –
Width mm(inch) 1275 (50-3/16) 875 (34-29/64) –
Depth mm(inch) 690 (27-5/32) 320 (12-38/64) –
Packing dimension
Height mm(inch) 360 (14-11/64) 761 (29-61/64) –
Width mm(inch) 1340 (52-3/4) 1049 (41-19/64) –
Depth mm(inch) 820 (32-9/32) 460 (18-7/64) –
Weight
(NET) k
g
(lb) 33 (73) 44 (97) –
(GROSS) k
g
(lb) 42 (93) 49 (108) –
Layers limit (actually) 9 (10) 3 (4) –
Operation condition
Cool (DBT) 18˚C – 32˚C -10˚C – 43˚C –
Heat (DBT) 16˚C – 30˚C -15˚C – 24˚C –
MAX WORKING PRESSURE HP/LP MPa (bar) 4.15/2.55 (41.5/25.5) –
P
I
P
I
N
G
Pipe diameter mm (inch)
(Liquid)ø9.52(3/8) (Gas)ø15.88(5/8) (Liquid)ø9.52(3/8) (Gas)ø15.88(5/8)
–
Connecting method, Standard length m(ft) ared type, 5.0(16.4) ared type, 5.0(16.4) –
Pipe length range m (ft) 3 – 40m (9.8 – 131.2) –
Indoor unit & Outdoor unit height difference m (ft) 15m(OD located lower)/30m(OD located higher) (49.2/98.4) –
Add gas amount
g
/m (oz/ft) 35
g
/m
(0.376) –
Pipe length for additional gas m (ft) 30m (98.4) –
*1 In case it is necessary to indicate the air flow volume in (l/s), the value in (m³/min.) shall be multiplied by 16.7 and rounded down the decimal point.
*2 If the EUROVENT Certified models can be operated under the "extra-low"temperature condition, -7°C dry bulb and -8°C wet-bulb temperatures with rated voltage
230V shall be used.
*3 Network Impedance shall be applicable for EUROPE and CHINA models.
*4 The annual consumption is calculated by multiplying the input power at 230V(400V) by an average of 500 hours per year in cooling mode.
*5 EER and COP classification is at 230V(400V) only in accordance with EU directive 2002/31/EC.