1-14
1
1-3. Other Component Specifications
Outdoor Units U-200PE1E8
MODEL No.
Outdoor Unit
Power Transformer
Rated
VAC, HzSource
Secondary
Coil resistance
Ω
Thermistor (Coil / Air sensor): TH1, TH2, TH3, TH4
Resistance
kΩ
–10°C: 23.7±5% 20°C: 6.5±5%
–5°C:18.8±5% 30°C: 4.4±5%
0°C: 15.0±5% 40°C: 3.1±5%
5°C: 12.1±5% 45°C: 2.6±5%
10°C: 9.7±5% 50°C: 2.1±5%
Thermistor (Discharge gas sensor): TH5
Resistance
kΩ
60°C:12.4±5% 90°C: 4.6±5%
70°C: 8.7±5%100°C: 3.4±7%
75°C: 7.4±5%110°C: 2.5±7%
80°C: 6.3±5%120°C: 1.9±7%
85°C: 5.3±5%130°C: 1.5±7%
Relay (Comp. Magnetic Contactor)
VACCoil rated
VAC, AContact rating
Coil resistance (at 20°C)
Ω
Sol-Control-Valve
4 way valve
4 way valve
Electro magnetic coil
Thermal cut off temperature
Sol-control-valve
Magnetic coil
U-200PE1E8
–
–
–
–
–
–
KTM-35D-S1, DTN-C532G3H
CM-12
–
–
–
UKV-25D18
STF-0401G
STF-01AI518A1, AC 220-240 V, 50Hz / 60Hz
UKV-A053 (062), DC 12V